Nx-networks NX series Instrukcja Użytkownika Strona 45

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 86
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 44
Cabling and connections
45(86)
6
Figure 6-20. Jumper selection for NXOPTA1
!
WARNING
Check the correct positions of the jumpers. Running the motor
with signal settings different from the jumper positions will not
harm the frequency converter but may damage the motor.
!
NOTE
If the AI signal content is changed the corresponding board
parameter in
menu M7
must also be changed.
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
A B C D
Jumper block X1:
AI1 mode
AI1 mode: Voltage input; 0...10V
AI1 mode: Voltage input; 0...10V (differential)
AI1 mode: Voltage input; -10...10V
Jumper block X2:
AI2 mode
AI2 mode: 0...20mA; Current input
AI2 mode: Voltage input; 0...10V
AI2 mode: Voltage input; 0...10V (differential)
AI2 mode: Voltage input; -10...10V
Jumper block X3:
CMA and CMB grounding
CMB connected to GND
CMA connected to GND
CMB isolated from GND
CMA isolated from GND
CMB and CMA
internally connected together,
isolated from GND
= Factory default
Jumper block X6:
AO1 mode
AO1 mode: 0...20mA; Current output
AO1 mode: Voltage output; 0...10V
AI1 mode: 0...20mA; Current input
Przeglądanie stron 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 85 86

Komentarze do niniejszej Instrukcji

Brak uwag